PLCS 0730 Series — String Converter & Booster Integrated System
The PLCS 0730 Series combines a high-efficiency DC/AC inverter with an integrated step-up transformer for flexible deployment in medium-to-large-scale energy storage plants.
It is designed for 1500 V DC systems and provides stable 6.6 kV AC output.
Compact, liquid-cooled, and IP65-protected, this model offers superior performance, easy maintenance, and intelligent monitoring for long-term operation.
| Parameter | Value |
|---|---|
| Product Model | PLCS-0730-SC-6.6 |
| Application | String Converter with Integrated Step-up Booster |
| Maximum DC Voltage | 1500 V |
| Rated DC Voltage | 1100 V |
| DC Voltage Range | 600 – 1500 V |
| Maximum DC Current | 1100 A |
| Rated AC Output Power | 730 kVA |
| Rated AC Voltage | 6.6 kV ± 10 % |
| Rated AC Current | ≈ 64 A |
| Rated Frequency | 50 Hz / 60 Hz |
| Power Factor Adjustable Range | –1 ~ +1 |
| THD (at Rated Power) | < 3 % |
| Conversion Efficiency | ≥ 98.5 % |
| Isolation Type | Integrated Dry-type Transformer |
| Cooling Method | Liquid Cooling with Smart Control |
| Protection Level | IP65 (Converter) / IP54 (Booster Section) |
| Operating Temperature Range | –30 °C ~ +55 °C |
| Relative Humidity | 0 – 95 % (non-condensing) |
| Altitude Limit | ≤ 4000 m (derating > 2000 m) |
| Communication Interfaces | RS485 / CAN / Ethernet (Modbus RTU & TCP) |
| Fire Protection System | Perfluorohexanone / Water Mist Fire Suppression |
| Monitoring System | Integrated BMS + EMS Smart Monitoring and Control |
| Dimensions (W×H×D) | 3200 × 2300 × 2400 mm (typical) |
| Weight | ≈ 4.2 tons |
| Noise Level | < 65 dB(A) |
| Compliance & Standards | IEC 62933 / GB/T 34120 / CE / UL / UN38.3 |
| Protection Features | Over-voltage, Over-current, Over-temperature, Short-circuit, Isolation Monitoring |